24
Changing Operating Parameter
CAUTION
The following operation includes the changing of the trip points of voltage or frequency. Never open the front cover of the
solar power conditioner display except by an authorized installer.
To change the trip points, follow the instructions below.
Perform changes while PV module is generating power during the daytime of a sunny day. Refer to the table on page 28 of the
value. The default value is designated by bold character.
1. Stop the power conditioner manually.
Press POWER button if it is operating.
STOP will be displayed on the display.
BACK
LIGHT
DISPLAY
MODE
CO2
POWER
RESET
SOLAR POWER CONDITIONER DISPLAY
2. Remove the front cover of the display.
Refer to page 22.
3. Slide the both of two dip switches to SVC position with a narrow tool.
The first parameter number and its value appear on the display. If the display continues to
indicate STOP, one or both switches are left in INV position. In this mode, do not press POWER
button! (POWER is not indicated on the display. See below figure.), do not make the solar power
conditioner start operating. Confirm the both switches are in SVC position.