In choosing a location for the StarInverter, consideration should be given to the following
criteria:
The heat sink temperatures can exceed 158 degrees (70° C). The StarInverter
must be installed so that the top of the unit will not be contacted by persons.
The StarInverter is suitable for installation both indoors and outdoors and the
enclosure has been given a NEMA 3R rating.
When the StarInverter is installed outdoors, it should be shielded from rain and
direct sunlight, if possible.
The StarInverter is designed to handle the temperature extremes of most
climates. The operating and non-operating ambient temperature range is from
-25° C to 40° C.
The following clearances are recommended for proper placement of the
StarInverter:
A minimum 36 clearance between the bottom of the inverter box and
the ground.
Visibility of the operating LED’s and display located at the top front of
the inverter box should also be considered.
If the inverter is to be installed in an enclosed space, adequate ventilation must
be provided.
2.2 Mounting the StarInverter
The StarInverter should be mounted vertically to a flat, solid surface such as wallboard,
concrete or wood siding. The inverter should be located in close proximity to the solar
panels to minimize the DC wire length.
The mounting bracket provided makes mounting the StarInverter quick and simple. The
two screw holes at either end of the bracket are 16 inches apart. Once the wall studs are
located, anchoring the bracket becomes an easy task.
WARNING: Prior to drilling holes to mount the StarInverter in the location
selected, ensure there are no electrical wires or plumbing in the area.
CAUTION:
The National Electrical Code (NEC) requires that the inverter be connected to a dedicated
circuit with no other outlets or devices connected to the same circuit. See NEC Section
690-64(b)(1). The NEC also places limitations on the size of the inverter and the manner
in which it is connected to the utility grid. See NEC Section 690-64(b)(2).