DC Input
* The maximum open-circuit voltage which can occur at a cell temperature of 10°C, must not exceed the maximum input voltage.
AC Output
Maximum DC power at cos φ = 1 3 200 W
Maximum input voltage* 600 V
MPP voltage range 268 V … 480 V
Rated input voltage 350 V
Minimum input voltage 268 V
Start input voltage 330 V
Maximum input current 12 A
Maximum input current per string 12 A
Number of independent MPP inputs 1
Strings per MPP input with ESS 3
Strings per MPP input 1
Rated power at 230 V, 50 Hz 2 750 W
Maximum apparent AC power 3 000 VA
Rated mains voltage 230 V
Nominal AC voltage 220 V/230 V/240 V
AC voltage range 160 V … 265 V
Nominal AC current at 220 V 12.5 A
Nominal AC current at 230 V 12.0 A
Nominal AC current at 240 V 11.5 A
Maximum output current 15.0 A
Total harmonic factor of output current at
AC THF voltage < 2%,
AC power > 0.5 AC rated power
≤3%
Rated power frequency 50 Hz
AC power frequency 50 Hz/60 Hz
Operating range at AC power frequency 50 Hz 45.5 Hz … 54.5 Hz
Operating range at AC power frequency 60 Hz 55.5 Hz … 64.5 Hz
Power factor at rated power 1
Feed-in phases 1