PVI 3000S, 4000S, 5000S, 5300 Series Inverters
Installation and Operation Manual (Rev A)
1
1
2.0 Site Preparation and Inverter Placement
The inverter is comprised of a rainproof NEMA 3R industrial enclosure containing electrical and
electronic components.
NOTE: If the inverter is mounted outside, during the installation process and in case of
rain, do not open the inverter.
Criteria for device mounting:
• Because the inverter is in a NEMA 3R enclosure, the
inverter can be mounted outdoors.
• The longest inverter life can be achieved by mounting it in a clean, dry and cool location. It is
recommended to keep the unit out of direct rain or snow. Protection by a roof overhang or
covering is recommended if outdoor mounting is necessary.
• For optimal electrical system efficiency, use the shortest possible AC and DC cables and use
the maximum allowable cable size.
• Avoid installation in close proximity to people or animals, as there is an audible high-
frequency switching noise.
• Install the inverter in an accessible location following local codes. Note that code
requirements for clearances and proximity to other equipment and building walls apply.
• For optimal inverter life and performance, do not mo
unt the inverter in direct sunlight,
especially in hot climates. If the unit must be mounted in direct sunlight, a silver or white
metal sun-shield is highly recommended. It is further recommended that the inverter be
mounted on the north or east side of buildings or on the northern side of a ground mounted
PV array. Following these guidelines help prevent the unit from limiting the power produced
due to an excessively high inverter temperature.