PVI 3000S, 4000S, 5000S, 5300 Series Inverters
Installation and Operation Manual (Rev A)
6
5
Ensure that the inverter is off and de-energized from both AC and DC sides.
Open the wiring box and inverter cover.
As shown in Figure 10.5.1, the JP14 and JP15 jumpers need to be placed at the
higher positions to set to positive grounding.
The red DC wire, that connects the inverter board to the wiring box, needs to be
connected to “Grounded” DCIN- terminal on the Inverter board.
The black wire, that connects the inverter to the wi
ring box, needs to be
connected to “Ungrounded” DCIN+ terminal on the Inverter board.
Disconnect the black DC wires (from PV array) connected to “GROUNDED
CONDUCTOR” terminal block.
Disconnect the red DC wires (from PV array) connected to “UNGROUNDED
CONDUCTOR” terminal block.
o If using the bypass terminals, disconnect the wires from the associated
terminal block.
Connect the black DC wires (from PV array) to the “UNGROUNDED CONDUCTOR”
terminal.
o If using the bypass terminals, connect the black DC wires to this set of
terminals.
Connect the red DC wires (from PV array) to the “GROUNDED CONDUCTOR”
terminal.
Add permanent weatherproof labels over the Ungrounded (+) and Grounded (-)
labels below the green terminal blocks. The left terminal block must be labeled
“Ungrounded (-)“ and the right terminal block must be labeled “Grounded (+)”.
Optional: add “Warning, Positively Grounded Unit” label to outside of unit at
bottom right corner of wiring box. (a label kit is available from Solectria if
requested).
Tighten the set screws to a torque of 1.7Nm (15.6 in
-lb.))