16
Installation
Note!
Need not connect the input terminal to optimizer.
● AC Output
SolarRiver series inverters are designed for single phase grid. Operating AC voltage range from 180V to
260V (200V-270V for Australia) and the typical frequency is 50Hz. Other operating parameters should
comply with local public grid regulations.
MCB with rated fault current of 30 mA≤I
fn
≤300 mA should be installed between inverter and grid. No load
should be connected directly with the inverter.
Table 4 Cable and MCB Requirement
Model
Cable (Cu)
MCB
SolarRiver
1100TL
SolarRiver
1600TL
SolarRiver
2300TL
SolarRiver
3000TL
SolarRiver
3300TL
SolarRiver
3680TL
SolarRiver
4400TL
SolarRiver
5200TL
1.5mm² 2.5mm² 4mm² 4mm² 4mm² 4mm² 4mm² 4mm²
10A 16A 20A 20A 25A 25A 25A 32A
Figure 13 AC Cable Loss for SolarRiver 3300TL
Length
0.0%
0.2%
0.4%
0.6%
0.8%
1.0%
1.2%
1.4%
Loss
0m
10m 20m
30m
40m 50m
60m
70m
80m
90m
100m
2.5mm
2
4.0mm
2
10.0mm
2
6.0mm
2
8.0mm
2
SolarRiver inverters come with good quality IP66 AC connector. Please refer to information below to make
correct AC connection.
Impedance of the AC connection should be less than 2Ω. To ensure anti-islanding function PV cable should
ensure power loss to be <1% of nominal power. Also AC cable between inverter and connection point
should be less than 150m. Chart below provides relationship between AC cable length and cross section
with losses.
Figure 12 Incorrect connections between Load and Inverter