Operation
23
Fault Information
Others
Output Voltage Vac=xxx.xV
Output Frequency Freq.=xx.xHz
Output Current Iac=xx.xA
PV Input Voltage Vpv= xxxV
PV Input Current Idc= xxx A
Isolation Fault Isolation Fault
Leakage Detecting Ground I Fault
Grid Fault
Fault OVR
Fault UVR
Fault OFR
Fault UFR
No Utility No Utility
Fan Fault Fan Fault
PV Over Voltage PV Over Voltage
Consistent Fault Consistent Fault
Relay Failur Relay Failure
DC INJ High DC INJ High
EEPROM Failure EEPROM Failure
SCI Failure SCI Failure
High DC Bus High DC Bus
DC Sensor Fault DC Sensor Fault
GFCI Failure GFCI Failure
Lock Lock
Reconnect Reconnect
Inverter’s Version Ver xx.xx
Output voltage
Output frequency
Output Current
PV input voltage
PV input current
Grounding fault or surge voltage protection failure
Leakage current over rating
AC Over voltage rating
AC Under voltage rating
AC Over frequency rating
AC Under frequency rating
No Utility
Fan locked or circuit fault
PV voltage ≥ Max.DC voltage
CPU or other hardware failure
Relay between grid and inverters failed
DC injection in AC output over rated value.
EEPROM’s failure
MCU internal communication failure
DC bus voltage is higher than the set value
Input DC detector failure
Leakage current detecting circuit failure
Frozen information
Reconnect to grid after relay disconnect
Version information