PV Powered 5200 Especificações Página 27

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 96
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 26
26 DOCR 070366-B
4.2 Utility AC voltage
The Solectria PVI Inverters must never be connected to a
120 V
ac
utility service. NEC 690.64(b)(1) requires that the inverter
be connected to a dedicated circuit with no other outlets or devices
connected to the same circuit.
CAUTION!
PRUDENCE!
Gridcongurationsallowed:
Figure 17: 208V Delta AC Grid
Voltage range for 208 V nominal, line to line 183 V - 228 V
Voltage range for 240 V nominal, line to line 211 V - 264 V
Frequency Range 59.3 Hz - 60.5 Hz
AC connection voltage and frequency limits:
Table 3: AC connection voltage and frequency limits
Figure 16: 240V/120V Split Phase AC Grid
The Solectria PVI inverters operate grid-tied to the utility voltage. PVI inverters are software con-
gurable via the user display panel for various 208 V
ac
or 240 V
ac
60 Hz service congurations as
shown in gures 16-22.
PVI Inverter
PVI Inverter
PVI Inverter
PVI Inverter
Vista de página 26
1 2 ... 22 23 24 25 26 27 28 29 30 31 32 ... 95 96

Comentários a estes Manuais

Sem comentários