42 DOCR 070366-B
Figure 35: Wiring box AC assembly – terminal labeling
Stranded copper wire should be checked for all strands inside the
terminal opening.
A
B
D
PE Terminal (AC System Ground)
N Terminal
L2 Terminal
L1 Terminal
GET (Grounding Electrode Terminal)
E
B
A
C D
E
C
NOTICE!
AVIS!
WARNING!
AVERTISSEMENT!
An additional external AC disconnect may be required by your
local AHJ. Please check local regulations to determine if the AC
disconnect is required for your installation.
AC-side
Terminals
1. Mount the external AC disconnect (if required by local AHJ) near the inverter.
2. Install conduit tting and conduit into the wiring box compartment from AC disconnect or
utility service panel.
3. Route AC wiring through conduit and verify that the exposed wires are at least 6 inches
in length to provide adequate strain relief and wire end strip length. Secure the conduit into
both ttings then tighten conduit ttings to manufacturer’s recommended torque.
4. Terminate inverter’s AC output wires inside the AC disconnect or junction box.
– Connect the AC system GND wire to the PE screw terminal (A) and using a 3/16“ (4
mm) at blade cabinet screw driver tighten the screw terminal to to 10.5 in-lbs (1.2 Nm)
of torque.