PV Powered 5200 Especificações Página 41

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 96
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 40
40 DOCR 070366-B
0.5 inch
Conduit ttings need to be water tight with either a NEMA 4, 4X, 6, or 6X rating.
Once conduit and ttings are installed, route wiring through the conduit and tting and allowing a
6 inch strain relief loop within the wiring box compartment.
Determine the AC voltage loss in the AC wires for a given wire cross section and wire length. The
following pages contain diagrams for each PVI inverter model to help determine the best wire size
for your particular installation. Solectria recommends that you select a wire size and length to en-
sure a maximum voltage. Please note that the diagrams only show approximate voltage loss and
more precise voltage loss should be calculated by a licensed electrician in accordance with local,
state, and National Electrical Code ANSI/NFPA 70 requirements. The conductor size shall not be
smaller than the 75
0
C wire size based on the ampacities given in table 310.16 of the NEC, ANSI/
NFPA 70 and an addtional derating factor of 125% as indicated by UL1741.
Figure 32: Conduit installation and AC wiring routing
6 inches
Vista de página 40
1 2 ... 36 37 38 39 40 41 42 43 44 45 46 ... 95 96

Comentários a estes Manuais

Sem comentários