38 DOCR 070366-B
It is worth noting that for this example we calculated the minimum series fuse rating. However, it
may be appropriate to use the supplied 15 A fuses as long as they do not exceed the maximum
series fuse rating (provided by the module manufacturer) or the overcurrent protection require-
ments of your PV source wires. Please reference the appropriate NEC Article(s) for further discus-
sion regarding proper sizing of overcurrent protection.
Other fuse manufacturers may have compatible fuse types. The generic properties are:
Type: PV Fuse
Fast-acting
Dimensions: 1 1/2” in length x 13/32” fuse diameter
Interrupt Rating: >= 10 kA @ 600 V
dc
UL and CSA approval of the fuse is mandatory
4.8.5.2 String fuse replacement
4.8.5.1.2 PV fuse properties
DANGER!
DANGER!
String fuses shall only be replaced by a qualied professional.
Ensure no live voltages are present on PV input and AC output
circuits, and verify that the DC disconnect, AC disconnect, and
dedicated AC branch circuit breaker are in the “OFF” position,
before attempting to replace DC fuses. With a DC amperage clamp
meter, ensure that there is no current owing through the fuse to be
replaced.
PV solar arrays produce hazardous voltages and currents when
exposed to light which can create an electrical shock hazard. Using
dark opaque sheets, cover the PV solar array before tampering or
reinserting PV string fuses
WARNING!
AVERTISSEMENT!
1 2
43
Figure 31: String fuse replacement procedure