95
PVP250kW & PVP260kW Inverter
Installation & Operation Manual
The following table lists the voltage faults, including VAC sense, VDC and power supply
faults.
Hexadecimal
Value
Display String Description
0001 VAC OVER PEAK A Peak AC voltage high, phase A
0002 VAC OVER PEAK B Peak AC voltage high, phase A
0004 VAC OVER PEAK C Peak AC voltage high, phase A
0008 PLL FAULT Control PLL fault
0010 AC UNBALANCED FAULT AC voltages unbalanced
0020 DC OVER VOLTAGE DC voltage high
0040 POWER SUPPLY P5 5V power supply fault
0080 POWER SUPPLY P15 15V power supply fault
0100 POWER SUPPLY M15 -15V power supply fault
0200 POWER SUPPLY 10 10V power supply fault
0400 POWER SUPPLY 24 24V power supply fault
0800 POWER SUPPLY 48 48V power supply fault
1000 DC PRECHARGE DC precharge fault
2000 PV-DC DELTA PV input and DC bus voltage delta
Table D-5 Voltage Fault (VLT)
The grid faults in the following table include grid interactive voltage and frequency faults.
Hexadecimal
Value
Display String Description
0001 AC FAST UNDERVOLT A Fast AC voltage low, phase A
0002 AC FAST UNDERVOLT B Fast AC voltage low, phase B
0004 AC FAST UNDERVOLT C Fast AC voltage low, phase C
0008 AC SLOW UNDERVOLT A Slow AC voltage low, phase A
0010 AC SLOW UNDERVOLT B Slow AC voltage low, phase B
0020 AC SLOW UNDERVOLT C Slow AC voltage low, phase C
0040 AC FAST OVERVOLT A Fast AC voltage high, phase A
0080 AC FAST OVERVOLT B Fast AC voltage high, phase B
0100 AC FAST OVERVOLT C Fast AC voltage high, phase C
0200 AC SLOW OVERVOLT A Slow AC voltage high, phase A
0400 AC SLOW OVERVOLT B Slow AC voltage high, phase B
0800 AC SLOW OVERVOLT C Slow AC voltage high, phase C
1000 AC UNDER FREQ Low frequency fault
2000 AC OVER FREQ High frequency fault
Table D-6 Grid Fault (GRD)
The following table lists the temperature faults.