59
PVP250kW & PVP260kW Inverter
Installation & Operation Manual
Response Information
Response
Layout
Modbus slave address nn (1-126)
Command number 11h
Number of bytes of data n
Data 1 xx
Data 2 xx
Data n xx
CRC LSB xx
CRC MSB xx
Table 5-14 Format for Return Slave ID, response to command 11h
Modbus Register Maps
The following tables list the Modbus registers with their location and a description of the
data stored in the register. For more information describing the data format contained in
column six, the “Format” column of each table, see Table 5-22 at the end of this chapter.
Description
Start
Register
End
Register
Nbr. of
Registers
MB
Address
Format Range Notes
Modbus base address = 0
Inverter ID number 0 7 8 40001 ASCII 16 char.
Unique number
for each inverter
Firmware version 8 11 4 40009 ASCII 8 char. Example: V1.9
Map version 13 13 1 40014 UINT 16 1 - 4
Increment se-
quentially as the
map changes
- all versions are
backwards com-
patible.
Inverter congura-
tion
14 14 1 40015 UINT 16
Bit-
mapped
See Table 5-16
Inverter serial
number
15 24 10 40016 ASCII 20 char. Matches SN label
Table 5-15 Fixed information registers
Inverter Conguration Bit Mapping Instructions
AC volts = 480 0x0004
AC volts = 600 0x0200
Transformer tap position 0x0008 Set if Tap at 265V, clear if Tap at 295V (Default = 295V)
Transformer wiring conguration 0x0010 Set if wired as DELTA, clear if wired as WYE (Default = WYE)
Utilitimeter installation ag 0x0100
Set if meter is installed, clear if not installed (Default = not
installed)
Table 5-16 Inverter Configuration