84
Characteristic
PVP250kW
(600VAC)
PVP250kW
(480VAC)
PVP260kW
(480VAC)
PVP260kW-LV
(480VAC)
Limits of accuracy time measurement +/- 0.1 sec
Enclosure rating NEMA 4
Dimensions (H x W X D in inches) 93 1/2 x 98 7/8 x 41 3/8
Maximum weight (lbs) 5,000
Relative humidity (%) 0-95%, non-condensing
Maximum heat rejection rate (BTU/hr) 41,000
Maximum blower air ow rate (CFM) 2,300
Altitude (ft) 6,000
Display VFD 4x20
Interface options RS232 & Ethernet
Communications protocol RS-485, IP over Ethernet
Standard warranty 10 years
Certications & Compliances
1,2
UL1741, CSA107.1-1, IEEE519, IEEE929,
IEEE1547, FCC Class A
Construction Powder coated steel with hot-dipped zinc base
Isolation transformer Yes
Startup power (W) 1,800
Noise emission (dBA) 3 - typical value at full load
< 65 dBA at 8 ft
< 59 dBA at 50 ft
Options
UL approved positive grounding Yes
Commercial grade data monitoring solutions Yes
Preventative maintenance program Yes
Extended warranty - 20 year Yes
Range of integrated fused sub-array combiners
from one to nine fuses from 75 to 600 Amps
Yes
Table A-1 Product Specifications Data
Notes:
1. The PVP250kW and PVP260kW Inverters comply with FCC Part 15 Class A conducted requirements. Radiated will be tested at a
later date and will be tested to CISPR, not FCC.
2. The PVP250kW and PVP260kW Inverters are designed to meet or exceed NEC Article 690 and UL1741-2005 Static Inverters
and Charge Controllers for use in Photovoltaic Power Systems, which includes testing for IEEE 1547.1-2005, IEEE 929-2000
and IEEE519-2000.
3. Declared Single-Number Noise Emission Values in Accordance with ISO 4871. dBA = A-weighted time average sound pressure
level, LpAd in decibels. 50 ft. data is extrapolated from the 8 ft. data.
Limits:
Limits of accuracy of voltage measurement and energy production measurements +/- 5%
Limits of accuracy of frequency measurement +/- 0.1Hz