ampacity, temperature and conduit. In addition wire should be sized to minimize voltage
drop. Install the inverter on a dedicated branch circuit with a recommended circuit
breaker rating as specied in the following table. Refer to Table D-10 in Appendix D for
more information.
Model 480VAC 600VAC
PVP250kW 400A 350A
PVP260kW 400A N/A
PVP260kW-LV 400A N/A
Table 4-1 Branch Breaker Size Recommendations
The inverter does not have internal AC fusing so it is important to size the branch circuit
protection appropriately.
When an inverter is installed on an electrical panel of the sizes indicated in Table 4-2, the
corresponding operational voltage range is provided in the second column.
Electrical Panel
Operational Voltage Range
480VAC 422VAC – 528VAC
600VAC 528VAC - 660VAC
Table 4-2 Operational Voltage Ranges per Electrical Panel
Voltages outside this range will cause the inverter to fault.
Connecting to the Electrical Grid
!
DANGER
Make sure the main breaker at the AC service panel is switched OFF before
connecting the AC wires to the inverter. This breaker should be switched ON
only after all wiring has been properly connected.
!
DANGER
Assurez-vous que le disjoncteur principal du panneau de service CA est en
position HORS TENSION avant de brancher les câbles CA à l’onduleur. Le
disjoncteur doit être en position SOUS TENSION une fois tous les câbles
branchés.
!
CAUTION
To avoid an increase in AC voltage to unacceptable values while the inverter
is connected, the grid impedance value at the connection point should be as
low as possible. By keeping the grid impedance value low, the system will
achieve higher efciency.