42
DC Wiring Procedure
Follow these steps to wire the DC inputs from the PV panels to the inverter. These
instructions are for a negatively grounded array. For a positively grounded array, use the
opposite terminals. Refer to Figure 4-14.
!
DANGER
Risk of Electrical Shock. When exposed to light, PV arrays create electrical
energy that could cause a hazardous condition.
!
DANGER
Risque d’électrocution. Lorsqu’elles sont exposées à la lumière, les piles
photovoltaïques génèrent un courant électrique susceptible de causer des
conditions dangereuses.
1. If the protective plastic covers which protect the DC subcombiner panel are in place,
remove the covers with a 5/32 Allen wrench.
2. Disconnect power to the DC wiring by disconnecting the PV array outside the in-
verter before starting the DC wiring.
3. Keep track of the array positive and negative leads and clearly mark each.
4. Route the PV array leads through the conduit to the desired entry gland plate on the
DC side of the inverter.
5. Connect the PV frame ground wire(s) to the ground lug on the point marked
in
the lower left side of the cabinet.
6. Connect positive DC lead(s) to the positive terminals located on the busbar or fuse
holder as applicable. Refer to Figure 4-14. Use Grade 8 3/8” hardware to secure the
lugs of the incoming DC cables to the busbar. The DC landing torque spec is 40 ft-
lbs.
7. Connect negative DC lead(s) directly to the negative terminals located on the busbar
or fusing as shown in Figure 4-14. Use Grade 8 3/8” hardware to secure the lugs of
the incoming DC cables to the busbar. The DC landing torque specication is 40 ft-
lbs.
8. Energize the DC cables.