PVP250kW & PVP260kW Inverter
Installation & Operation Manual
The following list provides the status codes and their meaning.
Status Flash Code
Normal Operation On steady, no ashing
Serial Communication Fault Short-Long-Short
DNS Failure Long-Short-Short
Network Connection Fault Short-Short-Long
Table 7-1 Status LED Flash Codes
Status LED Code Descriptions
Normal Operation
: Inverter communications are operating normally.
Serial Communication Fault: The communication PCB in the inverter communicates
with the inverters main processor via serial communication. If the communication PCB
cannot establish communication with the main processor, the Serial Communication
Fault code will ash.
Note: It is normal for this status code to ash for a few seconds during startup.
DNS Failure: The inverter uses a DNS (Domain Name Service) server to resolve the IP
address of the PV Powered database when it posts the data, once every 15 minutes. If the
DNS server cannot be found, or does not return a valid IP address, the DNS Failure code
will ash for a minute or so while the inverter is trying to post. After several retries, the
inverter will try to force a post to a hardcoded IP address. If this post succeeds, the LED
will go back to normal operation until the next post again tries to connect to the DNS
server.
Network Connection Fault: This status code ashes when the inverter cannot post data
to the PV Powered database server. The Network Connection Fault status code starts
ashing only after the inverter has tried to post data to the PV Powered server. The Status
LED may indicate normal operation before this occurs. This can happen in the following
circumstances:
The network cable is not connected.
The network does not have a DHCP server or the DHCP server did not give a valid
IP address to the inverter.
The PV Powered server is down for maintenance.
Any other network problem that does not allow the post to make it to the PV Pow-
ered server.
Modbus LED Operation and Signaling
If the inverter is connected as a slave device on a Modbus network, the Modbus LED
will ash quickly whenever there is activity on the network. The quick ashes will be
seen even if the Modbus commands are not addressed to the inverter. These quick ashes
enable the installer to troubleshoot the system by verifying that communications are
occurring on the network. If the inverter sees and responds to a message that is addressed
Vista de página 94