52
Step 2: Using Jumpers to Set the Pins for RS-485 Installation
By default, the termination pins have three slave jumpers installed in the J6/Master
positions and three jumpers in the J7/Slave positions when the inverter is shipped. The
location of the jumpers can determine the following settings to an inverter:
Terminate the network
Set jumpers for the center inverter(s) on the network
Turn on biasing
Jumper setting options
A. Terminate the network.
The performance of your Modbus network may require each end of the network
to be terminated using 120 ohm termination resistors. When the network is
long, relative to the RS-485 bit rate in use, bus terminations must be installed.
The network length is determined by the total backbone cable length, and not
necessarily the line-of-sight between the two furthest apart devises.
RS-485 / Modbus
Bit Rate
Maximum Network Length
without Termination
Feet (Meters)
Maximum Network Length
with Termination
Feet (Meters)
9600 bps 1000 (305) 4000 (1200)
19200 bps 500 (152) 4000 (1200)
38400 bps 250 (76) 4000 (1200)
57600 bps 150 (46) 4000 (1200)
Table 5-1 Maximum Network Length per Modbus Bit Rate
If bus termination is desired and the inverter is on the end of the Modbus
network, you may use the built-in bus termination resistors.
To enable an inverter’s bus termination, place the J7 “Line” jumper on its
outboard pins. See Table 5-2 for the pin locations.
J6 J16 J7
High X
Line X
Low X
Table 5-2 Termination Enabled (for End Device)