62
When multiple errors are set, the resulting status word value will be a sum of the
individual fault and/or error values listed in the following table.
Description
Hex
Value
Decimal
Value
Notes
Modbus register number = 42005
OK 0 0
Rebooting 1 1
Inverter communication fault 2 2
Results in return value of zero for reads of data
registers listed in Table 5-17.
Web post fault 4 4
DNS server fault 8 8
Real time clock error 10 16
Battery is dead or cannot synchronize with the net-
work time server.
Wrong PVM rmware 20 32
Incompatible or incorrect revision of communica-
tions rmware.
Table 5-21 Inverter Data Comm Status Word
Data Format Description Notes
ASCII Two ASCII characters per register
For a text string the left most character is
in the lowest register number.
UINT16 Unsigned integer: 16 bits Range: 0 to 65535
SINT16 Signed integer: 16 bits Range: -32767 to +32767
UINT 32 (requires two registers) Unsigned integer: 32 bits Range: 0 to 4,294,967,295
SINT 32 (requires two registers) Signed integer: 32 bits
Range: -2,147,483,647 to
+2,147,483,647
FLOAT (requires two registers)
IEEE 754 standard 32-bit oating
point number
Table 5-22 Data formats for registers
Information about the Data Monitoring Module
For additional information on how to use the Modbus Data Monitoring Module, contact
PV Powered Customer Service and Technical Support at 1-877-312-3832.