7.4 Maintaining the Card Cage Air Filter
The card cage features a secondary air lter to ensure long PCB life. The card cage air
lter is located under the intake air shroud above the card cage which is located on the
right side of the power module assembly in the upper cabinet.
Use the following instructions to access the secondary air lter and refer to Figure 7-3.
1. Remove the air intake shroud above the card cage. This will expose the air lter.
2. Remove the four screws on the card cage air lter.
3. Clean the lter with compressed air.
4. Once the lter is cleaned, replace the lter and shroud.
If the lter needs to be replaced, call PV Powered Technical Support at 1-877-312-3832,
Figure 7-3 Card Cage Air Filter
7.5 Faults and Warnings
The display screen is the primary indicator of a possible problem with the inverter. If a
fault has occurred the inverter will cease power production until the fault is cleared. A
fault may be a latching or non-latching fault. A non-latching fault will be automatically
cleared if the fault condition is resolved and the inverter will restart automatically after
completing its startup sequence. A latching fault requires manual intervention to restart
the inverter.
If the inverter has faulted, the display screen will show the corresponding fault
information in a series of three or more screens.
• The rst screen – displays the fault code(s)
• The second screen – displays a text description of the fault(s).
• The third screen – displays technical support contact information.
Card Cage Air Filter
Card Cage Air Shroud
Retainer Screws