PVP250kW & PVP260kW Inverter
Installation & Operation Manual
!
PRUDENCE
An d’éviter des surtensions inacceptables de CA lorsque l’onduleur est
branché, assurez-vous que la valeur de l’impédance aux points de connexion
au réseau public est la plus basse possible. Une faible valeur d’impédance
permet un fonctionnement plus efcace de l’appareil.
The inverter is connected to the electrical grid using four wires:
Phase A voltage
Phase B voltage
Phase C voltage
Ground
Do NOT connect a neutral wire to the WYE point of the isolation transformer.
The four AC termination busbars for phases A, B, C and ground are located in the lower
right of the AC panel. Refer to Figure 4-2. The phase busbars are vertically mounted and
the ground busbar is horizontally mounted at the bottom of the cabinet. Each busbar has
seven rows of two 3/8” diameter holes, spaced 1” apart vertically.
The AC connections must be made through the user selected gland plates (plates and
dimensions are shown in
Appendix C - Mechanical Drawings
).
DC +
DC-
Ground
Phase A
Phase B
Phase C
Ground
DC + and DC- Phase A, B, C and Ground
Figure 4-14 DC and Phase Inverter Connections