The inverter is connected to the electrical grid using four wires:
• Phase A voltage
• Phase B voltage
• Phase C voltage
• Ground
Do NOT connect a neutral wire to the WYE point of the isolation transformer.
The four AC termination busbars for phases A, B, C and ground are located in the lower
right of the AC panel. Refer to Figure 4-2. The phase busbars are vertically mounted and
the ground busbar is horizontally mounted at the bottom of the cabinet. Each busbar has
seven rows of two 3/8” diameter holes, spaced 1” apart vertically.
The AC connections must be made through the user selected gland plates (plates and
dimensions are shown in
Appendix C - Mechanical Drawings
).