PVP250kW & PVP260kW Inverter
Installation & Operation Manual
!
DANGER
Ne branchez pas les conducteurs photovoltaïques positifs ou négatifs à la
barre omnibus de mise à la terre fournie. Les piles PV sont mises à la terre
grâce au GFDI intégral. Mettre les conducteurs positifs ou négatifs à la terre à
tout autre point du système ne permettrait pas au circuit de protection contre
les mises à la masse défectueuses de fonctionner normalement.
The inverters can also be ordered with an optional fused subcombiner. The standard
busbar has two rows of 3/8” holes for lug connections. The fused subcombiners have
individual input terminals for each fuse block. These terminals require the use of a torque
wrench to properly install the chosen interface cables. For proper torque values of DC
subcombiner box wire mounting hardware, see
Appendix D - Limits, Fault Codes, Torque
Values, and Wire Sizes
.
The inverters are factory congured with either a three-phase 480VAC or three-phase
600VAC output (PVP260kW is 480VAC only). The inverter is interfaced with the utility
grid at the AC landing within the AC section on the front right side of the inverter. These
terminals require the use of a UL-approved crimp-on type ring terminal or a UL-approved
compression type lug certied for use with the chosen interface cables. Ensure similar
cables run together in conduit runs and through gland plates, which allows any inductive
currents produced to be cancelled out. For proper torque values of terminal lugs mounting
hardware, see
Appendix D - Limits, Fault Codes, Torque Values, and Wire Sizes.
!
CAUTION
Risk of Equipment Damage. There shall be no connection of the AC Neutral
terminals (H0 and X0) on the main transformer. These connections shall be
left oating.
!
PRUDENCE
Risque d’endommagement matériel. Aucun branchement ne doit être effectué
sur les bornes neutres de CA (H0 et X0) du transformateur principal. Ces
bornes doivent être libres de tout branchement.
This equipment is intended to be installed as part of a permanently grounded electrical
system as per the NEC (Canadian Electrical Code for Canada) and ANSI/NFPA 70 or
applicable state or local standards. A copper clad earth grounding electrode must be
installed within three feet (one meter) of the unit. The AC ground busbar located in the
AC section, lower front cabinet, must be used as the single point connection to the earth
grounding electrode for the inverter system.
AC overcurrent protection for the utility interconnect (grid-tied) must be provided by
installers as part of the installation. The following overcurrent protection device ratings
are recommended: